HVAC control system
HVAC (Heating, Ventilation and Air Conditioning) equipment needs a control system to regulate the operation of a heating and/or air conditioning system.[1] Usually a sensing device is used to compare the actual state (e.g. temperature) with a target state. Then the control system draws a conclusion what action has to be taken (e.g. start the blower).
Direct digital control
Central controllers and most terminal unit controllers are programmable, meaning the direct digital control program code may be customized for the intended use. The program features include time schedules, set points, controllers, logic, timers, trend logs, and alarms. The unit controllers typically have analog and digital inputs that allow measurement of the variable (temperature, humidity, or pressure) and analog and digital outputs for control of the transport medium (hot/cold water and/or steam). Digital inputs are typically (dry) contacts from a control device, and analog inputs are typically a voltage or current measurement from a variable (temperature, humidity, velocity, or pressure) sensing device. Digital outputs are typically relay contacts used to start and stop equipment, and analog outputs are typically voltage or current signals to control the movement of the medium (air/water/steam) control devices such as valves, dampers, and motors.
Groups of DDC controllers, networked or not, form a layer of systems themselves. This "subsystem" is vital to the performance and basic operation of the overall HVAC system. The DDC system is the "brain" of the HVAC system. It dictates the position of every damper and valve in a system. It determines which fans, pumps, and chiller run and at what speed or capacity. With this configurable intelligence in this "brain", we are moving to the concept of building automation.[2]
Building automation system
More complex HVAC systems can interface to Building Automation System (BAS) to allow the building owners to have more control over the heating or cooling units.[3] The building owner can monitor the system and respond to alarms generated by the system from local or remote locations. The system can be scheduled for occupancy or the configuration can be changed from the BAS. Sometimes the BAS is directly controlling the HVAC components. Depending on the BAS different interfaces can be used.[4]
Today, there are also dedicated gateways that connect advanced VRV / VRF and Split HVAC Systems with Home Automation and BMS (Building Management Systems) controllers for centralized control and monitoring, obviating the need to purchase more complex and expensive HVAC systems. In addition, such gateway solutions are capable of providing remote control operation of all HVAC indoor units over the internet incorporating a simple and friendly user interface.[5]
Cost and efficiency
Many people do not have a Heating, Ventilation, and Air Condition (HVAC) system in their homes because it is too expensive. However according to this article Save Money Through Energy Efficiency, HVAC is not as expensive as one may think it is.[6] Although many might choose to not believe that sticker and that it is just there to help with the sales, history shows that many of the newer HVAC systems with the yellow energy guide stickers help save customers hundreds to thousands of dollars depending on how much they use their HVAC system.[citation needed]
On the yellow energy guide sticker on many of the newer systems, it displays the average cost to run that machine. Once a customer has found the perfect HVAC system, the customer should run it monthly if it is only put into use during specific times of year. It is recommended that if an HVAC system is not being used each month, that it should be turned on and left running for ten to fifteen minutes.[citation needed]
On the other hand if the customer is somebody who runs their HVAC system frequently, it is really important to maintain it. Maintenance on an HVAC system includes changing out the air filter, inspecting the areas where air intake takes place, and check for leaks.[citation needed]
Doing these three steps are super essential and is the key to keeping an HVAC system running for a long time. A customer should do these three steps every couple of months or when it is suspected problem with the HVAC system.[citation needed]
Some signs that could lead to a potential problem is if the HVAC system does not provide air cool enough.[citation needed]
That could be due to a leakage in the cooling fluids. Another sign that could mean that the HVAC system is not running perfectly fine is if there is a bad smell to the air that it is providing. That often means that the air filters need to be replaced. Changing the air filters on an HVAC system is really important because they are exposed to a lot of dust depending on where your HVAC system is and it could build up dust from simply just sitting in one's home.
Goals HVAC system installation
Source[7]
Goal 1: Keep HVAC equipment and materials dry during construction and provide temperature and humidity control as required during the close-in phase of construction. HVAC System Installation
Goal 2: Install HVAC systems to effectively implement moisture control as specified in the design drawings and specifications. HVAC System Installation
Goal 3: Prepare operation and maintenance materials for continued performance of HVAC system moisture control.
Design, modeling, and marketing
Most HVAC systems are used for the same purpose but designed differently.[citation needed]
All HVAC systems have an intake, air filter, and air conditioning liquid. However, when designing HVAC systems, many engineers design it for a specific setting and/or purpose. When engineers are designing an HVAC system, they try their best to make it compact while still being able to perform at the highest level and experiment with different ways to make HVAC systems as efficient as possible.
History
The first HVAC controllers utilized pneumatic controls since engineers understood fluid control. Thus, the properties of steam and air were used to control the flow of heated or cooled air via mechanically controlled logic.
After the control of air flow and temperature was standardized, the use of electromechanical relays in ladder logic to switch dampers became standardized. Eventually, the relays became electronic switches, as transistors eventually could handle greater current loads. By 1985, pneumatic controls could no longer compete with this new technology although pneumatic control systems (sometimes decades old) are still common in many older buildings.[8]
By the year 2000, computerized controllers were common. Today, some of these controllers can even be accessed by web browsers, which need no longer be in the same building as the HVAC equipment. This allows some economies of scale, as a single operations center can easily monitor multiple buildings.
See also
- American Society of Heating, Refrigerating and Air-Conditioning Engineers
- BACnet
- Building Automation
- OpenTherm
References
- ^ US EPA, OAR (2014-10-17). "Heating, Ventilation and Air-Conditioning Systems, Part of Indoor Air Quality Design Tools for Schools". www.epa.gov. Retrieved 2024-08-13.
- ^ "Role on DDC Systems in Building Commissioning". Archived from the original on 2020-05-06. Retrieved 2009-05-19.
- ^ Coffin, Michael J. (2012-12-06). Direct Digital Control for Building HVAC Systems. Springer Science & Business Media. ISBN 978-1-4615-4921-5.
- ^ KMC Controls. "Understanding Building Automation and Control Systems". Archived from the original on 19 May 2013. Retrieved 12 March 2017.
- ^ "CEDIA Find: Cool Automation Integrates Smart Air Conditioners with Third-Party Control Systems". CEPro. Archived from the original on 17 June 2015. Retrieved 16 Jun 2015.
- ^ Noor, Dharna (2023-07-29). "Air conditioning: the benefits, problems and alternatives". The Guardian. ISSN 0261-3077. Retrieved 2024-08-13.
- ^ Moisture Control Guidance for Building Design, Construction and Maintenance. U.S. Environmental Protection Agency. December 2013.
- ^ KMC Controls. "Pneumatic to Digital: Open System Conversions" (PDF). Retrieved 5 October 2015.
- v
- t
- e
concepts
- Air changes per hour
- Bake-out
- Building envelope
- Convection
- Dilution
- Domestic energy consumption
- Enthalpy
- Fluid dynamics
- Gas compressor
- Heat pump and refrigeration cycle
- Heat transfer
- Humidity
- Infiltration
- Latent heat
- Noise control
- Outgassing
- Particulates
- Psychrometrics
- Sensible heat
- Stack effect
- Thermal comfort
- Thermal destratification
- Thermal mass
- Thermodynamics
- Vapour pressure of water
- Absorption-compression heat pump
- Absorption refrigerator
- Air barrier
- Air conditioning
- Antifreeze
- Automobile air conditioning
- Autonomous building
- Building insulation materials
- Central heating
- Central solar heating
- Chilled beam
- Chilled water
- Constant air volume (CAV)
- Coolant
- Cross ventilation
- Dedicated outdoor air system (DOAS)
- Deep water source cooling
- Demand controlled ventilation (DCV)
- Displacement ventilation
- District cooling
- District heating
- Electric heating
- Energy recovery ventilation (ERV)
- Firestop
- Forced-air
- Forced-air gas
- Free cooling
- Heat recovery ventilation (HRV)
- Hybrid heat
- Hydronics
- Ice storage air conditioning
- Kitchen ventilation
- Mixed-mode ventilation
- Microgeneration
- Passive cooling
- Passive daytime radiative cooling
- Passive house
- Passive ventilation
- Radiant heating and cooling
- Radiant cooling
- Radiant heating
- Radon mitigation
- Refrigeration
- Renewable heat
- Room air distribution
- Solar air heat
- Solar combisystem
- Solar cooling
- Solar heating
- Thermal insulation
- Thermosiphon
- Underfloor air distribution
- Underfloor heating
- Vapor barrier
- Vapor-compression refrigeration (VCRS)
- Variable air volume (VAV)
- Variable refrigerant flow (VRF)
- Ventilation
- Water heat recycling
- Air conditioner inverter
- Air door
- Air filter
- Air handler
- Air ionizer
- Air-mixing plenum
- Air purifier
- Air source heat pump
- Attic fan
- Automatic balancing valve
- Back boiler
- Barrier pipe
- Blast damper
- Boiler
- Centrifugal fan
- Ceramic heater
- Chiller
- Condensate pump
- Condenser
- Condensing boiler
- Convection heater
- Compressor
- Cooling tower
- Damper
- Dehumidifier
- Duct
- Economizer
- Electrostatic precipitator
- Evaporative cooler
- Evaporator
- Exhaust hood
- Expansion tank
- Fan
- Fan coil unit
- Fan filter unit
- Fan heater
- Fire damper
- Fireplace
- Fireplace insert
- Freeze stat
- Flue
- Freon
- Fume hood
- Furnace
- Gas compressor
- Gas heater
- Gasoline heater
- Grease duct
- Grille
- Ground-coupled heat exchanger
- Ground source heat pump
- Heat exchanger
- Heat pipe
- Heat pump
- Heating film
- Heating system
- HEPA
- High efficiency glandless circulating pump
- High-pressure cut-off switch
- Humidifier
- Infrared heater
- Inverter compressor
- Kerosene heater
- Louver
- Mechanical room
- Oil heater
- Packaged terminal air conditioner
- Plenum space
- Pressurisation ductwork
- Process duct work
- Radiator
- Radiator reflector
- Recuperator
- Refrigerant
- Register
- Reversing valve
- Run-around coil
- Sail switch
- Scroll compressor
- Solar chimney
- Solar-assisted heat pump
- Space heater
- Smoke canopy
- Smoke damper
- Smoke exhaust ductwork
- Thermal expansion valve
- Thermal wheel
- Thermostatic radiator valve
- Trickle vent
- Trombe wall
- TurboSwing
- Turning vanes
- Ultra-low particulate air (ULPA)
- Whole-house fan
- Windcatcher
- Wood-burning stove
- Zone valve
and control
- Air flow meter
- Aquastat
- BACnet
- Blower door
- Building automation
- Carbon dioxide sensor
- Clean air delivery rate (CADR)
- Control valve
- Gas detector
- Home energy monitor
- Humidistat
- HVAC control system
- Infrared thermometer
- Intelligent buildings
- LonWorks
- Minimum efficiency reporting value (MERV)
- Normal temperature and pressure (NTP)
- OpenTherm
- Programmable communicating thermostat
- Programmable thermostat
- Psychrometrics
- Room temperature
- Smart thermostat
- Standard temperature and pressure (STP)
- Thermographic camera
- Thermostat
- Thermostatic radiator valve
trades,
and services
- Architectural acoustics
- Architectural engineering
- Architectural technologist
- Building services engineering
- Building information modeling (BIM)
- Deep energy retrofit
- Duct cleaning
- Duct leakage testing
- Environmental engineering
- Hydronic balancing
- Kitchen exhaust cleaning
- Mechanical engineering
- Mechanical, electrical, and plumbing
- Mold growth, assessment, and remediation
- Refrigerant reclamation
- Testing, adjusting, balancing
organizations
- Indoor air quality (IAQ)
- Passive smoking
- Sick building syndrome (SBS)
- Volatile organic compound (VOC)
- ASHRAE Handbook
- Building science
- Fireproofing
- Glossary of HVAC terms
- Warm Spaces
- World Refrigeration Day
- Template:Home automation
- Template:Solar energy