Zone valve
A zone valve is a specific type of valve used to control the flow of water or steam in a hydronic heating or cooling system.
In the interest of improving efficiency and occupant comfort, such systems are commonly divided up into multiple zones.[1] For example, in a house, the main floor may be served by one heating zone while the upstairs bedrooms are served by another. In this way, the heat can be directed principally to the main floor during the day and principally to the bedrooms at night, allowing the unoccupied areas to cool down.
This zoning can be accomplished in one of two ways:
- Multiple circulator pumps, or
- A single circulator pump and zone valves.
Zone valve construction and operation
Zone valves as used in home hydronic systems are usually electrically powered. In large commercial installations, vacuum or compressed air may be used instead. In either case, the motor is usually connected to the water valve via a mechanical coupling.
For electrical zone valves, the motor is often a small shaded-pole synchronous motor combined with a rotary switch that can disconnect the motor at either of the two stopping points ("valve open" or "valve closed"). In this way, applying power to the "open valve" terminal causes the motor to run until the valve is open while applying power at the "close valve" terminal causes the motor to run until the valve is closed. The motor is commonly powered from the same 24 volt ac power source that is used for the rest of the control system. This allows the zone valves to be directly controlled by low-voltage thermostats and wired with low-voltage wiring. This style of valve requires the use of an SPDT thermostat or relay.
A simpler variant of the motorized design omits the switch that detects the valve position. The motor is simply driven until the valve hits a mechanical stop, which stalls the motor. In an alternative design, the motor continues to turn, while a slip clutch allows the valve to be pushed against a mechanical stop. Usually, the valve remains open as long as power is supplied, and a strong spring closes it when power is cut. This simpler design consumes electrical power whenever the valve is open. There is no feedback to verify the state of the valve, which is assumed to do what has been commanded.
Zone valves can also be constructed using wax motors and a spring-return mechanism. In this case, the valve is normally closed by the force of the spring but can be opened by the force of the wax motor. Removal of electrical power re-closes the valve. This style of zone valve operates with a perfectly ordinary SPST thermostat.
For vacuum- or pneumatically operated zone valves, the thermostat usually switches the pressure or vacuum on or off, causing a spring-loaded rubber diaphragm or ball valve to move and actuate the valve.[2] Unlike the switch-monitored electrical zone valves, these valves automatically return to the default position without the application of any power, and the default position is usually "open", allowing heat to flow.
Highly sophisticated systems may use some form of building automation such as BACnet or LonWorks to control the zone valves.
Comparison with multiple circulator pumps
Multiple zones can be implemented using either multiple, individually controlled circulator pumps or a single pump and multiple zone valves. Each approach has advantages and disadvantages.
Multiple pump system
Advantages:
- Lower total cost of ownership when zone valve failure and repair costs are taken into account.
- More robust and reliable system.
- Simple mechanical and control design ("SPST thermostats")
- Redundancy: If one zone pump fails, the others can remain working
- Far superior method of linking multiple heat sources. Such as gas and solid fuel in one system.
Disadvantages:
- Higher initial installation cost. Circulator pumps cost more than zone valves
- Higher power consumption. Operating circulators draw more power any time the zone is actively heating. Zone valves, by comparison, draw little power at any time and many designs only draw power while in transition from open to close or vice versa.
Zone valve system
Advantages:
- Lower initial installation cost.
- Lower power consumption.
- Ease of maintenance certain models.
Disadvantages:
- Zone valves operated by electric timing motors aren't "fail safe" (failing to the "open" condition).[2]
- No inherent redundancy for the pump. A zone-valved system is dependent upon a single circulator pump. If it fails, the system becomes completely inoperable.
- The system can be harder to design, requiring both "SPDT" thermostats or relays and the ability of the system to withstand the fault condition whereby all zone valves are closed simultaneously.
- Zone valves increase the pressure drop through the system, to varying degrees. Care is required during system design to achieve proper flow rates with zone valves.
Selected manufacturers
See also
References
- ^ McElwain (January 26, 2001). "Troubleshooting Hot Water Zone Valves". ACHR News. Retrieved February 2, 2024.
- ^ a b Joy, Anju Thangam (July 20, 2023). "A Guide to Zone Valves". Tameson. Retrieved February 2, 2024.
- v
- t
- e
concepts
- Air gap (plumbing)
- Backflow
- Compatibility (chemical)
- Corrosion
- Drain (plumbing)
- Drinking water
- Fuel gas
- Friction loss
- Grade (slope)
- Greywater
- Heat trap
- Hydrostatic loop
- Leak
- Neutral axis
- Onsite sewage facility
- Pressure
- Sanitary sewer
- Sewer gas
- Sewage
- Sewerage
- Siphon
- Storm sewer
- Stormwater
- Surface tension
- Tap water
- Thermal expansion
- Thermal insulation
- Thermosiphon
- Trap (plumbing)
- Venturi effect
- Wastewater
- Water hammer
- Water supply network
- Water table
- Well
- Brazing
- British Standard Pipe (BSP)
- Cast iron pipe
- Chemical drain cleaners
- Compression fitting
- Copper tubing
- Crimp (joining)
- Drain-waste-vent system
- Ductile iron pipe
- Flare fitting
- Garden Hose Thread (GHT)
- Gasket
- Hydronics
- Leak detection
- National Pipe Thread (NPT)
- Nominal Pipe Size (NPS)
- O-ring
- Oakum
- Pipe (fluid conveyance)
- Pipe dope
- Pipe support
- Plastic pipework
- Push-to-pull compression fittings
- Putty
- Sealant
- Sewage pumping
- Soldering
- Solvent welding
- Swaging
- Thread seal tape
- Threaded pipe
- Tube bending
- Water heat recycling
- Atmospheric vacuum breaker
- Automatic bleeding valve
- Automatic faucet
- Backflow prevention device
- Ball valve
- Bleed screw
- Booster pump
- Butterfly valve
- Check valve
- Chemigation valve
- Chopper pump
- Circulator pump
- Cistern
- Closet flange
- Concentric reducer
- Condensate pump
- Coupling (piping)
- Diaphragm valve
- Dielectric union
- Double check valve
- Eccentric reducer
- Expansion tank
- Faucet aerator
- Float switch
- Float valve
- Floor drain
- Flow limiter
- Flushing trough
- Flushometer
- Gate valve
- Globe valve
- Grease trap
- Grinder pump
- Hose coupling
- Manifold
- Needle valve
- Nipple (plumbing)
- Pinch valve
- Piping and plumbing fitting
- Plug (sanitation)
- Pressure regulator
- Pressure vacuum breaker
- Pressure-balanced valve
- Pump
- Radiator (heating)
- Reduced pressure zone device
- Reducer
- Relief valve
- Riser clamp
- Rooftop water tower
- Safety valve
- Sewage pump
- Street elbow
- Submersible pump
- Tap (valve)
- Thermostatic mixing valve
- Trench drain
- Vacuum breaker
- Vacuum ejector
- Valve
- Water tank
- Zone valve
- Accessible bathtub
- Bathtub
- Bidet
- Dehumidifier
- Dishwasher
- Drinking fountain
- Electric water boiler
- Evaporative cooler
- Flush toilet
- Garbage disposal unit
- Hot water storage tank
- Humidifier
- Icemaker
- Instant hot water dispenser
- Laundry tub
- Shower
- Sink
- Storage water heater
- Sump pump
- Tankless water heater
- Urinal
- Washing machine
- Washlet
- Water dispenser
- Water filter
- Water heater
- Water softener
and control
trades,
and services
organizations
and standards
- Fire sprinkler system
- Piping
- Template:HVAC
- Template:Public health
- Template:Sewerage
- Template:Toilets
- Template:Wastewater